Rack Power Inputs

Bus Current
--
Busbar Cross-Section
--
Recommended Busbar
--
Current at 800V DC
--
Busbar at 800V DC
--
Copper vs 800V HVDC
--

Simplified engineering estimate - confirm with vendor data.

Formula & Assumptions

This tool converts rack power to bus current and estimates copper busbar cross-section using simplified engineering formulas:

  • Current: DC / single-phase I = P(kW) × 1000 ÷ V; 3-phase AC I = P × 1000 ÷ (√3 × V × PF).
  • Busbar area: S = I ÷ J, where J is the busbar current density: 1.5 A/mm² for enclosed busway, 2.0 A/mm² for typical open busbar, 2.5 A/mm² with forced cooling.
  • Recommended size: smallest standard busbar (15×3 to 125×10 mm) that covers the required cross-section.
  • 800V HVDC comparison: higher bus voltage means lower current and proportionally less copper — the core reason 800V DC distribution cuts busbar mass.

Disclaimer: Simplified estimate for architecture-level comparison. Peak currents, temperature rise, installation method and vendor data must be confirmed during detailed design.